Report ID: 852 Published: 1 October 2019 Region: CROSS-UK

This report is over 2 years old

Please be aware that it might contain information that is no longer up to date. We keep all reports available for historic reference and as learning aids.

Overview

This report highlights how a reporter discovered rotted CLT roof panels during the investigation of a roof that had been leaking for a few years.

Key Learning Outcomes

For architects and designers:

  • Be aware of the risks associated with moisture build-up in buildings, in particular ones where the timber is the main form of construction

  • Proper detailing can be key to controlling condensation in buildings

  • BS 5250:2011 Code of practice for control of condensation in buildings gives guidance on the risks associated with excessive humidity in buildings, notably mould growth and condensation

Full Report

Find out more about the Full Report

The Full Report below has been submitted to CROSS and describes the reporter’s experience. The text has been edited for clarity and to ensure anonymity and confidentiality by removing any identifiable details. If you would like to know more about our secure reporting process or submit a report yourself, please visit the reporting to CROSS-UK page.

 

The reporter was asked to check the roof of a building which had been leaking for a few years. The building in question was still occupied. The roof consisted of flat cross-laminated timber (CLT) panels. Falls were provided by firring pieces with insulation and supporting marine ply under the single ply membrane.

As part of their investigation, CLT panels on the roof, parapets and terrace were exposed. Inspection found that not only was the ply under the membrane rotten, but areas of CLT had also severely rotted. The reporter was shocked to see that in some areas, three of the typical five plies in the CLT panels had rotted through both on parapets and roof panels. Rotting of a CLT panel can be seen in Figure 1.  Sloping sections of roof with the membrane on top of insulation seemed fine.

Image
Figure 1: rotting of a CLT panel

The risk of hidden water in timber structures

The reporter speculates that the issue is due to hidden water entrapped between an impervious roof membrane and the effectively impervious CLT panels. They were told that the roof had been allowed to become wet during construction, but it is not clear if the water which caused the rotting developed during construction or was allowed in following construction due to incorrect design and detailing.

The reporter speculates that the issue is due to hidden water entrapped between an impervious roof membrane and the effectively impervious CLT panels

The remedial works for the heavily damaged areas resulted in replacement of much of the flat roof areas using parallel chord timber trusses with metal webs for the longer spans, with more traditional joists used elsewhere. Less damaged areas were repaired by replacing the ply under the membrane, and in other areas, steel beams were connected to the CLT wall panels with shear rings cut into the panels.

Expert Panel Comments

Find out more about the Expert Panels

Expert Panels comment on the reports we receive. They use their experience to help you understand what can be learned from the reports. If you would like to know more, please visit the CROSS-UK Expert Panels page.

CLT, like timber in general, will rot when excess moisture is present over long periods of time. It is worth considering how the CLT became exposed to water in the first place. The reporter speculates that the water could have developed during construction. It could also be due to condensation, or leaks in the waterproof membrane, or both.

It should be assumed that water vapour will pass through the CLT and into the construction above, unless specially treated to be impervious. With an impervious roof covering, such as the single ply membrane in this case, there are two ways in which the roof could be constructed; either with a cold deck or a warm deck.

Are warm deck roofs the preferred option?

The 2002 Building Research Establishment (BRE) report Thermal insulation: avoiding risks states that the preferred option is a warm deck roof. The cold deck roof is considered a poor option in the temperate, humid climate of the UK, where sufficient ventilation may not be achieved in sheltered locations or in windless conditions, even when the roof is correctly designed

Controlling condensation in buildings

What the reporter describes could be condensed water vapour dripping back into the building due to poor detailing or construction of the roof covering. BS 5250:2011 Code of practice for control of condensation in buildings gives guidance on the risks associated with excessive humidity in buildings, notably mould growth and condensation. Both can compromise the integrity of the building fabric. It describes the principal sources of water vapour, its transportation and deposition, and provides guidance on how to manage those risks during design, construction and operation.

The benefits and limitations of CLT

The 2011 BRE paper CLT - An introduction to low-impact building materials provides a broad view of the benefits and limitations of CLT for those considering its use in construction projects.

The 2011 BRE paper CLT - An introduction to low-impact building materials provides a broad view of the benefits and limitations of CLT for those considering its use in construction projects

This report also highlights a theme that occurs in many CROSS reports which is of ‘inspectability’. The object of an inspection is to detect a problem before it progresses far enough to become structurally dangerous. In this case, it looks as if there was no way of telling that the timber was rotting until degradation had progressed too far. With a trend for increasingly greater use of CLT in buildings, including tall buildings, it is important to ensure protection of the material from water and from other potential hazards.